Troubleshooting• Check the servo drive current consumption.• Avoid simultaneous acceleration of all servo drives.• Decrease the acceleration value.9.2.2.6 DC link Overpower (Error 0x2313/0x161)This fault applies to the PSM 510.Possible Causes• The PSM 510 was operating at over 140% of the nominal power rating for too long.Troubleshooting• Check the current consumption.9.2.2.7 PT Power Overload (Error 0x2314/0x162)This fault applies to the PSM 510.Possible Causes• The PSM 510 was operating at 100–140% of the nominal power rating for too long.Troubleshooting• Check the current consumption.9.2.2.8 UAUX Overcurrent (Error 0x2391/0x125)This fault applies to the DAM 510.Possible Causes• The servo drives are consuming more power on the UAUX line than allowed.Troubleshooting• Check the number of attached servo drives with the shell diagrams in the VLT® Servo Drive System ISD 510, DSD 510, MSD 510Design Guide.• Avoid simultaneous lifting of the servo drive brakes.9.2.2.9 UAUX Overvoltage (Error 0x3292/0x133)This fault applies to the DAM 510.Possible Causes• Incorrect UAUX supply.DiagnosticsOperating Guide | VLT® Multiaxis Servo Drive MSD 510 SystemAQ262450196490en-000101 / 175R1170| 169Danfoss A/S © 2019.10