102 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 0477..22..66 DDiissppllaayy MMeennuu OOppeerraattiioonnTable 33 describes the menu functions and how to use them.Table 33. Display Menu OperationFunction Subfunction OperationHome An overview of UPS operation, including information on load, efficiency andconsumption.Meters – UPS The meter screens show the UPS meter readings for the unit. The default voltagedisplayed on these screens is phase-to-neutral. These can be changed to displaythe voltage phase-to-phase (A-B, B-C, C-A). Tap the METERS tab on the mainmenu navigation bar to display the METER SUMMARY screen (see Figure 50).The current UPS readings are displayed in the information area of the screen. Todisplay individual meter details, tap the desired meter button to display thedetailed meter screen.Output – UPS The Output screen shows output voltage (phase to neutral), output current (eachphase), and frequency being supplied by the UPS, as well as the kVA, kW, andpower factor measurements.Input – UPS The Input screen shows input voltage (phase to neutral), input current (eachphase), and frequency of the incoming utility source, as well as the kVA, kW, andpower factor measurements.Bypass The Bypass screen shows the bypass input voltage (phase to neutral), inputcurrent (each phase), and frequency of the incoming utility source, as well as thekVA, kW, and power factor measurements.Battery – UPS The Battery screen displays the battery voltage (Vdc) and the battery current(Idc).Mimics UPS Mimic Tap the MIMICS tab on the main menu navigation bar to display an overview ofUPS operation, including information on load, efficiency and consumption. Ifthere is an error, an error indicator is displayed next to the affected part. Activeevents log can be opened by tapping the error indicator.UPS Module Map Tap the UPS MODULE MAP tab on the secondary menu navigation bar todisplay the status of each UPM.System Overview Tap the SYSTEM OVERVIEW tab on the secondary menu navigation bar todisplay the status and meters summary for each UPS.ESS Tap the ESS tab on the secondary menu navigation bar to display theapproximate consumption and energy savings of ESS mode.Logs Active Tap the LOGS tab on the main menu navigation bar to display the ACTIVEEVENTS screen (see Figure 51). A listing of all system events that are currentlyactive is displayed. The most recent event is listed first. As events clear, they areremoved from the Events listing. To scroll through the events, press the up ordown scroll bar.System Log (Historical) Tap the SYSTEM LOG tab on the secondary menu navigation bar to display theSYSTEM LOG screen (see Figure 52). The history Log lists up to 512 events inchronological order, with the most recent event listed last (once 512 is reached,the earliest event is overwritten). The end of the log (the most recent events) isdisplayed first; scroll upward to view older event listings. To scroll through theevents, press the up or down scroll bar.UPS Operating Instructions