136 Eaton 93PM UPS (400V/480V Four-Wire – 100 kW Frame) Installation and Operation Manual 164000566—Rev 041100..22..11 UUPPSS IInnppuuttOperating Input Voltage Rectifier: 400 Vac Wye, 3W + ground. Neutral not used.Bypass: 400 Vac Wye, 4W + ground.orRectifier: 480 Vac Wye, 3W + ground. Neutral not used.Bypass: 480 Vac Wye, 4W + ground.Operating Input Frequency Range 50/60 HzOperating Input Current For 380 Vac UPS systems, see Table 5 through Table 7.For 400 Vac UPS systems, see Table 8 through Table 10.For 415 Vac UPS systems, see Table 11 through Table 13.For 480 Vac UPS systems, see Table 14 and Table 15.Reduced for GeneratorAdjustableInput Current Harmonic Content 3% THD at full loadPower Factor Minimum 0.99Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4Battery Voltage 240 cell – 480VdcBattery Charging Capacity 16.5 A maximum per 50 kW module at full load at nominal input voltage1100..22..22 UUPPSS OOuuttppuuttUPS Output Capacity 100% rated currentOutput Voltage Regulation ± 1% (10% to 100% load)Output Voltage 400 Vac Wye, 4W + groundor480 Vac Wye, 4W + groundOutput Voltage Harmonic Content 1.5% maximum THD (linear load)5% maximum THD (nonlinear load)Output Current For 380 Vac UPS systems, see Table 5 through Table 7.For 400 Vac UPS systems, see Table 8 through Table 10.For 415 Vac UPS systems, see Table 11 through Table 13.For 480 Vac UPS systems, see Table 14 and Table 15.Output Voltage Balance < 2% for 100% maximum load imbalance (linear load)Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load)Frequency Regulation 0.1 Hz free runningSynchronous to Bypass ± 4 Hz (default setting)Frequency Slew Rate 1 Hz per second (default setting)Product Specifications