STARTINGONLINEThe rectifier and inverter turn on. The DC voltage continues to ramp up tofull voltage. Once the DC link reaches full voltage and the battery breakeris closed, the UPS output relay K3 closes. Power is now supplied to thecritical load in the double conversion mode. It takes approximately 20seconds for the UPS system to achieve the double conversion mode.The UPS system is now operating in the double conversion mode and the greenstatus indicator for normal operation is illuminated.7.4.2 Shutting down a single UPSA single UPS in the system can be shut down only if it is redundant. In practice,this means that a UPS is not allowed to be shut down if doing so would lead toan overload condition in the remaining UPSs in the system.To shut down a single UPS:1. In the home screen, press Controls.The System controls screen is displayed.2. In the System controls screen, press UPS controls.3. In the UPS control screen, select Shut down UPS.7.4.3 Enabling and disabling the battery chargerTo turn the battery charger on or off, perform the following procedure:1. In the home screen, press Controls.The System controls screen appears.2. In the System controls screen, press UPS controls.3. Press the Turn on / Turn off button.7.5 UPM control instructions7.5.1 Starting the UPMsMake sure that the load level does not exceed the single UPM capacity.To start an individual power module in the double conversion mode:1. Open the UPS front door.2. If included inside the UPS system, check that the rectifier input switchesare closed.3. Check that the battery breaker is closed.4. Close the UPS front door.5. Close the UPS input feeder circuit breaker.6. Close the UPS bypass input feeder circuit breaker.Eaton 93PM UPS 30–200 kVA User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 101 (126)