Overload capabilityat ambient 40 °C(in the stored energy mode)10 min 102–110% load60 s 111–125% load300 ms > 126% loadOverload capabilityat ambient 40 °C(in the bypass mode)Continuous ≤ 125% load10 ms 1,000% loadNote! Bypass fuses may limit the overloadcapability.Load power factor (rated) Nominal 1.0Load power factor (permitted range) From 0.8 lagging to 0.8 leadingTable 24: Eaton 93PM 60 kVA / 54 kW UPS system output deviationsOverload capability atambient 30 °C(on inverter)10 min 102–110% load60 s 111–125% load60 s 126–150% load300 ms > 150% loadOverload capabilityat ambient 30 °C(in the stored energy mode)Continuous < 103% load60 s 103–105% load300 ms > 105% loadOverload capabilityat ambient 30 °C(in the bypass mode)Continuous ≤ 125% load60 s 103–105% loadNote! Bypass fuses may limit the overloadcapability.Load power factor (rated) Nominal 0.9Load power factor (permitted range) From 0.8 lagging to 0.8 leading9.4 UPS environmental specificationsAcoustic noise at 1 m 30–50 kW and 60 kVA: < 60 dBA80–200 kW: < 65 dBAESS operation: < 45 dBAAmbient UPS storage temperature range From -25 °C ... +55 °C in the protectivepackageInternal battery:+20 °C ... +25 °C in the protective packageAmbient operating temperature range, 30–200kW modelsFrom +5 °C ... +40 °C*Eaton 93PM UPS 30–200 kVA User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 113 (126)