CAUTIONTo reduce the risk of a fire, connect only to a circuit that is provided withmaximum input circuit breaker current ratings from Table10 and Table11 inaccordance with the national and local installation rules.The line-to-line unbalanced output capability of the UPS is limited only by the fullload per phase current values for AC output to critical load shown in Tables10and11 . The recommended line-to-line load unbalance is 50% or less.Source protection for the AC input to bypass must suit the characteristics of theload and take into account effects such as inrush or starting current.Bypass and output overcurrent protection and bypass and output disconnectswitches must be provided by the user.4.4 Unpacking and unloading the UPSBefore you start to unpack and unload the UPS, examine the TipNTell indicatoron the package surface and the DropNTell indicator on the UPS after unpacking(see step 2 below). If the equipment has been correctly transported in theupright position, the indicator should be intact. If the indicator arrow has turnedall blue, contact the appropriate parties to report inappropriate transportation.WARNINGThe UPS cabinet is heavy. If you do not obey the unpacking instructions, thecabinet can tip over and cause serious injury.Do not tilt the UPS cabinet more than 10 degrees from the vertical or thecabinet can tip over.For transportation purposes, the UPS cabinet is bolted onto a wooden pallet. Toremove the pallet:1. Before you unload the cabinetfrom the pallet, use a forklift orother material handlingequipment to move the cabinetto the installation area. Insertthe forks of the forklift betweenthe skids on the bottom of theunit.Eaton 93PM UPS 30–200 kVA User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 46 (126)