operating environment must meet the height, clearance, and environmentalrequirements specified.4.3.1 Environmental and installation considerationsThe UPS system can be installed where there is TN, TT, or IT power distributionsystem.• Install the system indoors on a level floor suitable for computer or electronicequipment. The floor must be suitable for heavy weight and wheeling.• Install the system in a temperature and humidity controlled area, where thedew point cannot be reached.• Install the system in an area that is free of conductive contaminants.• Install the cabinet either in line-up-and-match or standalone configurations.Failure to follow these guidelines may void your warranty.The UPS equipment operating environment must meet the weight requirementsshown in Table4 , and the size requirements shown in Table5 .Table 4: UPS cabinet maximum weights30–50 kW,60 kVA*80–100kW120–150kW160–200kWShipping weight[kg]910 380 490 590Installed weight[kg]860 330 405 535Floor loading[kg/m2]1760 640 790 1050* Note that with 30–50kW and 60kVA models, the maximum number of internal batteriesare included. Shipping weights may be lower based on accessories installed into UPS.Table 5: UPS cabinet dimensionsDimensions(W x D x H)30–150 kW,60 kVA [mm]160–200 kW[mm]160–200 kWwith Side IntegratedAccessory CabinetMBS [mm]Shipping dimensions 750 x 1135x 2050900 x 1135x 20351090 x 1135x 2050Cabinet dimensions 560 x 914x 1876760 x 914x 1876966 x 914x 1876Eaton 93PM UPS 30–200 kVA User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 37 (126)