4.2 Installation checklistAction Yes / NoAll packing materials and restraints are removed from each cabinet.Each cabinet in the UPS system is placed in its installed location.A cabinet grounding kit / mounting kit is installed between any cabinetsthat are bolted together.All conduits and cables are properly routed to the UPS and any ancillarycabinets.All power cables are properly sized and terminated.Neutral conductors are installed and bonded to ground according to therequirements.A ground conductor is properly installed.Battery cables are terminated and connected to battery connectors.Battery Shunt trip and Aux contact signal wiring is connected from theUPS to the battery breaker.LAN drops are installed.All LAN connections are completed.Air conditioning equipment is installed and operating correctly.There is sufficient workspace around the UPS and other cabinets.Sufficient lighting is provided around all the UPS equipment.A 230 VAC service outlet is located within 7.5 meters of the UPS equip-ment.The Remote Emergency Power-off (REPO) device is mounted in its in-stalled location and its wiring is terminated inside the UPS cabinet.If EPO is used in the NC configuration, a jumper is installed on the EPObetween pins 1 and 2.(OPTIONAL) Alarm relays and signal outputs are wired appropriately.(OPTIONAL) A remote battery disconnect control is mounted in its instal-led location and its wiring is terminated inside the UPS and battery cabi-net.(OPTIONAL) Accessories are mounted in their installed locations andtheir wiring is terminated inside the UPS cabinet.Start-up and operational checks are performed by an authorized EatonCustomer Service Engineer.4.3 Site preparationsFor the UPS system to operate at peak efficiency, the installation site must meetthe environmental parameters outlined in these instructions. If the UPS needs tobe operated at an altitude higher than 1,000 m, contact your servicerepresentative for important information about high altitude operation. TheEaton 93PM UPS 30–200 kVA User's and installation guide© Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 36 (126)