UPS MAINTENANCEEaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual P-164000500 Rev 4 www.eaton.com/powerquality9-2 When replacing batteries, use the same number of sealed, leadβacid batteries. Proper disposal of batteries is required. Refer to your local codes for disposalrequirements. Do not dispose of batteries in a fire. Batteries may explode when exposed toflame. Do not open or mutilate batteries. Released electrolyte is harmful to the skin andeyes. It may be toxic.9.2 Performing Preventive MaintenanceThe UPS system requires very little preventive maintenance. However, the systemshould be inspected periodically to verify that the units are operating normally andthat the batteries are in good condition.9.2.1 DAILY MaintenancePerform the following steps daily:1. Check the area surrounding the UPS system. Ensure the area is not cluttered,allowing free access to the unit.2. Ensure the air intakes (vents on the front door or panels) and the exhaustopenings (on top of the UPM section) are not blocked.3. Ensure the operating environment is within the parameters specified inparagraph 3.2.2 and Chapter 10, βProduct Specifications.β4. Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If analarm lamp is illuminated or the Normal status indicator is not illuminated, contactan Eaton service representative.9.2.2 MONTHLY MaintenancePerform the following steps monthly:1. Monitor system parameters as described in paragraph 7.3, βUsing the ColorTouchscreen Control Panelβ.2. Check the UPS air filters (located behind the front panels or door) and wash orreplace as necessary. See Figure 9β1 and Figure 9β2 for filter locations, andTable 9β1 for filter sizes. Contact an Eaton service representative for replacementfilters. To remove and replace the filters:Table 9β1. UPS Filter SizesFilter Location SizeBottom Left ISBM Section Air Filters (Continuous Static Switch) 12β20β0.25βBottom Right ISBM Section Air Filters (Continuous Static Switch) 12β20β0.25βMiddle Right ISBM Section Air Filter (Continuous Static Switch) 20β6.3β0.25βUPM Section Air Filters 20β44β0.25βC A U T I O NVerify washed filters are thoroughly dry before reinstalling.