UPS INSTALLATION PLAN AND UNPACKINGEaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual P-164000500 Rev 4 www.eaton.com/powerquality3-22Table 3‐14. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate BatteryBasic Unit RatingUnitsRating50/60HzRating50/60HzRating50/60HzRating50/60HzRating50/60HzRating50/60HzkVAkW6756757507508258259009001000100011001100Input and Output Voltage Volts 380/380 380/380 380/380 380/380 380/380 380/380AC Input to UPS Rectifier (0.98 Minimum pF)Full load current plus battery recharge current(3) Phases, (1) GroundMinimum Conductor SizeNumber per PhaseAAmps 1200 1363 1500 1600 1818 2000AWG orkcmil(each)500(5)500(6)500(6)500(6)500(8)500(8)AC Input to UPS Bypass (Five Wire)Full Load Current(3) Phases, (1) Neutral, (1) GroundBAmps 1026 1139 1253 1367 1519 1671Minimum Conductor SizeNumber per PhaseAWG orkcmil(each)500(5)500(5)500(5)500(6)500(6)500(8)DC Input from Each Battery Disconnect to Each UPS UPM(1) Positive, (1) NegativeMinimum Conductor SizeNumber per PoleCAmpsperUPM603 603 603 603 603 603AWG orkcmil(each)500(3)500(3)500(3)500(3)500(3)500(3)AC Output to Critical Load (Five Wire)Full Load Current(3) Phases, (1) Neutral, (1) GroundDAmps 1026 1139 1253 1367 1519 1671Minimum Conductor SizeNumber per PhaseAWG orkcmil(each)500(5)500(5)500(5)500(6)500(6)500(8)NOTE Callout letters A, B, C, and D map to Figure 6‐5 .Terminals E1A through E5A and E9A through E11A are stud type terminals. Theintercabinet power wiring connections for this equipment are rated at 90°C. SeeTable 3‐15 for intercabinet power cable terminations and Table 3‐16 for suppliedintercabinet wiring terminal hardware.The torque values listed in Table 3‐15 for the M8 studs are the maximum allowable.Tightening further will risk breaking or twisting the stud.Figure 4‐8 through Figure 4‐11 show the location of the intercabinet power cableterminals inside the UPS.