26User Manual MN040024ENEffective November 2016DX-NET-ETHERNET2-2 field bus connectionEtherNet/IP for variable frequency drive DE1/DC1EATON www.eaton.comTable 15. Class 0x44 Modbus (Read/Write indicted number of parameters from Instance)Drive Mode Type Inst. Readservice Maxsupported len Writeservice Maxsupported lenPara. Description— Field bus command R/W WORD 1 0x4E 30 0x50 1— Field bus speed reference value 0.1 Hz R/W S16 2 0x4E 29 0x50 1— Reserved R/W — 3 0x4E 28 0x50 1— Modbus ramp time R/W U16 4 0x4E 27 0x50 1— — R — 5 0x4E 26 — —— Status and fault word R — 6 0x4E 25 — —— Field bus actual speed R S16 7 0x4E 24 — —— Motor current R U16 8 0x4E 23 — —— Reserved R — 9 0x4E 22 — —— Reserved R — 10 0x4E 21 — —— DI status R Binary code 11 0x4E 20 — —— Type R WORD 12 0x4E 19 — —— Power R U16 13 0x4E 18 — —— Voltage level R U16 14 0x4E 17 — —— Control section software version R WORD 15 0x4E 16 — —— Power section software version R WORD 16 0x4E 15 — —— variable frequency drive recognition R WORD 17 0x4E 14 — —— Reserved R — 18 0x4E 13 — —— Reserved R — 19 0x4E 12 — —— Value AI1 R U16 20 0x4E 11 — —— Value AI2 R U16 21 0x4E 10 — —— Reference input speed R S16 22 0x4E 9 — —— DC link voltage R U16 23 0x4E 8 — —— Variable frequency drive temperature R S16 24 0x4E 7 — —— Variable frequency drive operating time R — 25 0x4E 6 — —— Variable frequency drive operating time R — 26 0x4E 5 — —— The variable frequency drive operating timesince the last fault R — 27 0x4E 4 — —— The variable frequency drive operating timesince the last fault R — 28 0x4E 3 — —— — R — 29 0x4E 2 — —— — R — 30 0x4E 1 — —P-01 Maximum frequency / maximum speed R/W U16 129 0x4E 53 0x50 1P-02 Minimum frequency / minimum speed R/W U16 130 0x4E 52 0x50 1P-03 Acceleration time (acc1) R/W U16 131 0x4E 51 0x50 1P-04 Deceleration time (dec1) R/W U16 132 0x4E 50 0x50 1P-05 Stop Function R/W U16 133 0x4E 49 0x50 1P-06 Energy optimization R/W U16 134 0x4E 48 0x50 1P-07 Nominal motor voltage R/W U16 135 0x4E 47 0x50 1P-08 Rated motor current R/W U16 136 0x4E 46 0x50 1P-09 Rated motor frequency R/W U16 137 0x4E 45 0x50 1P-10 Nominal speed of the motor R/W U16 138 0x4E 44 0x50 1P-11 Voltage amplification R/W U16 139 0x4E 43 0x50 1P-12 Control level R/W U16 140 0x4E 42 0x50 1P-13 Fault log history R/W U16 141 0x4E 41 0x50 1P-14 Access code (P-15 to P-53 A 101) R/W U16 142 0x4E 40 0x50 1P-15 Function of digital inputs R/W U16 143 0x4E 39 0x50 1P-16 Analog input 1 (AI1), signal range R/W U16 144 0x4E 38 0x50 1P-17 Pulse frequency R/W U16 145 0x4E 37 0x50 1P-18 K1 signal (Relay Output 1) R/W U16 146 0x4E 36 0x50 1P-19 K1-Limit value (relay) R/W U16 147 0x4E 35 0x50 1