27User Manual MN040024ENEffective November 2016DX-NET-ETHERNET2-2 field bus connectionEtherNet/IP for variable frequency drive DE1/DC1EATON www.eaton.comTable 15. Class 0x44 Modbus (Read/Write indicted number of parameters from Instance), continuedDrive Mode Type Inst. Readservice Maxsupported len Writeservice Maxsupported lenPara. DescriptionP-20 Fixed frequency FF1 / speed 1 R/W U16 148 0x4E 34 0x50 1P-21 Fixed frequency FF2 / speed2 R/W U16 149 0x4E 33 0x50 1P-22 Fixed frequency FF3 / speed 3 R/W U16 150 0x4E 32 0x50 1P-23 Fixed frequency FF4 / speed 4 R/W U16 151 0x4E 31 0x50 1P-24 Second deceleration time (dec2) R/W U16 152 0x4E 30 0x50 1P-25 AO1 signal (Analog Output) R/W U16 153 0x4E 29 0x50 1P-26 Frequency skip 1, bandwidth (hysteresis range) R/W U16 154 0x4E 28 0x50 1P-27 Frequency skip 1, center R/W U16 155 0x4E 27 0x50 1P-28 V/Hz characteristic curve modification voltage R/W U16 156 0x4E 26 0x50 1P-29 V/Hz characteristic curve modification frequency R/W U16 157 0x4E 25 0x50 1P-30 REAF, Start function with automatic restart,control signal terminals R/W U16 158 0x4E 24 0x50 1P-31 Start function with automatic restart,operating unit. R/W U16 159 0x4E 23 0x50 1P-32 DC current braking R/W U16 160 0x4E 22 0x50 1P-33 Motor pick-up control function (to catch spinningmotors) (in sizes FS2 and FS3) / DC braking,braking time at start (in size FS1)R/W U16 161 0x4E 21 0x50 1P-34 Brake chopper activation (in sizes FS2 and FS3) R/W U16 162 0x4E 20 0x50 1P-35 Analog input 1 scaling R/W U16 163 0x4E 19 0x50 1P-36 Serial communication configuration R/W U16 164 0x4E 18 0x50 1P-37 Access code definition R/W U16 165 0x4E 17 0x50 1P-38 Parameter access lock R/W U16 166 0x4E 16 0x50 1P-39 Offset for analog input 1 R/W U16 167 0x4E 15 0x50 1P-40 Speed display scaling factor R/W U16 168 0x4E 14 0x50 1P-41 PI controller, proportional gain R/W U16 169 0x4E 13 0x50 1P-42 PI controller, integral time R/W U17 170 0x4E 12 0x50 1P-43 PI controller, operating mode R/W U18 171 0x4E 11 0x50 1P-44 PI controller, reference value/setpoint value R/W U19 172 0x4E 10 0x50 1P-45 PI digital setpoint value R/W U20 173 0x4E 9 0x50 1P-46 PI controller, feedback R/W U21 174 0x4E 8 0x50 1P-47 Analog input 2 (AI2), signal range R/W U22 175 0x4E 7 0x50 1P-48 Standby-time R/W U23 176 0x4E 6 0x50 1P-49 PI controller, feedback wakeup level R/W U24 177 0x4E 5 0x50 1P-50 CANopen Baud rate R/W U25 178 0x4E 4 0x50 1P-51 Motor overload protection R/W U26 179 0x4E 3 0x50 1P-52 Parameter access R/W U27 180 0x4E 2 0x50 1P-53 Reaction to the communication fault R/W U28 181 0x4E 1 0x50 1