30 Analog input/output module ±10 V XN-322-8AIO-U230.5 Filtering:XN300 slice modules 02/24 MN050002EN Eaton.com 22830.5 Filtering:The low-pass cutoff frequency can be configured for each input channelusing the appropriate register. This cutoff frequency is specified in Hzwithout any decimal places.Example: 50 Hz low-pass cutoff frequency; register value: 50dec / 32 hexThe following settings are valid:30.6 Technical specifications30.6.1 Analog inputs ±10 V/0 – 100%Low-pass cut-off frequency Register valueFilter disabled (default) 0x00001 Hz 0x000110 Hz 0x000A25 Hz 0x001950 Hz 0 x0032100 Hz 0x0064250 Hz 0x00FA500 Hz 0x01F41000 Hz 0x03E8Number of channels 4Measurement type Differential input Potentiometer inputMeasuring range V -10 V ...+10 V 0 …100 % (potentiometer)Measurement display -10,000 ... +10,000 0 ... 10,000A-D converter Bit 16Resolution 0,3 mV / LSBConversion time per channel ms 1Common-mode range V ±12Input resistance M > 10Open wire monitoring YesInput filtersHardware Typically: 1 kHz, third-order low-pass filterSoftware, parameterizable parameterizableCumulative error as apercentage of full scale value% ±0.3 ±0.35