31 XN-322-4AIO-I analog input/output module31.4 Technical specificationsXN300 slice modules 02/24 MN050002EN Eaton.com 23831.4.3 External power supplyThe 24 VDC power supply is used to power the analog inputs and outputs.31.4.4 Measurement ranges31.4.5 DiagnosticsWhen it comes to the analog inputs, cable breaks will only be detected withdiagnostics when using the 4 – 20 mA measuring range. When using the 0 –20 mA measuring range, the open wire detection diagnostics will alwaysread "FALSE."Channels ValueNumber of supply voltages 1 (X3, pin on connector 24V)Supply voltage +24 V 18…30 VDCVoltage monitoring Supply voltage OK status LED U > 18 VDCMaximum power acceptance 70 mACurrentin mAValue representationin μA0 …20 mA 0000…20000 Represented as a decimal value4 … 20 mA 4000…20000→ Range and channel diagnostics must be taken into account inorder to ensure that the reading shown is being interpretedcorrectly.Diagnostics Measuring range in mA0 – 20 4 – 20Cable break – < 4 mA (diagnostics)Under Range – 0 … 4 mADisplay value Measured valueOver Range 20 …21 mAover current > 21 mADisplay value > 21 (no reading)