Outputs MenuPage 41Technical Alarm (06)Active when there is a technical alarm. Deactivates when the zone causing the alarmis restored AND a user enters a valid access code to acknowledge the technicalalarm alert.Confirmed Alarm (07)Active when there is a confirmed alarm. Deactivates when the system is reset. Theoperation of this output type depends on the option selected in System Options –Confirmation – Confirmation Mode (see page 62):RF Low Battery (08)Active when a wirefree detector reports a low battery. The output remains active untilall detectors stop reporting low batteries.RF Supervision (09)Active when there is a supervision failure on any radio zone. The output remainsactive until all supervision failures are reset.RF Jamming (10)Active when the control unit detects jamming. The output remains on until alljamming disappears and the system is reset.RF Fault (11)Active when there are any of the following faults: RF Low Battery, RF supervision, RFjamming and the system is reset.A/C Fail (12)Active when either mains power is absent, or a zone of type External PSU A/C Failhas been triggered. The action of this output depends on the value programmed inSystem Options – Mains Fail Delay (see page 75).Battery Fault (13)Active when the control unit detects a fault with its backup battery, or a zone of typeExternal PSU Battery Fault has been triggered. If the alert was caused by anExternal PSU Battery Fault zone, the control unit deactivates the output when thezone has been restored and a user has acknowledges the fault by entering a validaccess code.If the alert was caused by a fault with the control unit’s backup battery, the controlunit deactivates the output when it detects a good battery.Ext PSU Low Volts (14)Active when an external power supply has triggered an External PSU Low Voltszone.The control unit deactivates the output when the zone has been restored and a userhas acknowledges the fault by entering a valid access code.Ext PSU Fault (15)Active when an external power supply triggers a zone of type External PSU Fault.The control unit deactivates the output when the zone has been restored and a userhas acknowledges the fault by entering a valid access code.Tamper (16)Active when the control unit detects a tamper at the control unit (lid or back), or at aradio keypad, detector, sounder, or when there is an activation of a zone of typeTamper.The control unit deactivates the output when tamper is reset.