Lumina 35 Explanation control functions9The settings that have to be made for the tunnel part (T-part) correspond broadly with the settings for the M/MT-part. Instead of the ventilation position in % you enter the offset temperature for the positions. At the first positionthis offset temperature is linked to start temperature ventilation + calculated bandwidth. Each following position islinked to the previous position via an offset. In other words: the control computer never controls in between twopositions.M/MT-phaseExhaust InletsCtrl. Control-lable/ExtraRelays Inlet(%)Tun(%)Press. (Pa)Cap.(m3/h)ºC 1 2 3 1 2 3 4 5 6 7 8 9 10T1 2.0 0 0 0 1 1 1 1 1 1 0 0 0 0 50 25 0 120000T2 1.0 0 0 0 1 1 1 1 1 1 1 0 0 0 0 50 0 140000T3 1.0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 75 0 160000T4 1.0 0 0 0 1 1 1 1 1 1 1 1 1 0 0 100 0 180000T5 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0T10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0Modulating control can be used to control the ventilation level in percentages of a cycle time. The controlcomputer activates/deactivates the fans according to a fixed pattern. This supplies fresh air in short repeatedperiods. Modulating fans are shown in the combi-table by the letter M.Example: Modulating ventilationThe required ventilation position of the fans: 21%The control computer will control the fans on for 50% of the set cycle time. The ventilation is off for 50%of the time.Determining the ventilation positionThe control computer determines the use of air inlets, extra inlets and fans based on the combi-table. Theexample below shows a combi-table with modulating fans. The relay fans will do 20.000 m3 each.