Lumina 35 Installer35INSTALLER → VENTILATION → COMBI MTT → M/MT-phase (min) → tab page Cap.Position % Setting of the ventilation percentage at which fans should activate/deactivate and airinlets open/close. The ventilation percentages must increase from the lowest to thehighest position.The combi positions are also used for natural ventilation.Pressure Pa Setting of the required pressure for the corresponding position. A rule of thumb: thehigher the ventilation position, the lower the required pressure. Enter 0 to deactivatepressure control.Cap m³/h Setting of the ventilation capacity (m3/hour) for all positions used. If ventilation is usedin m3/hour/animal, always fill in this column!INSTALLER → VENTILATION → SETTINGS → tab page Miscell.Combi control Setting of the speed of progression to the next or previous position in the combi-table.Choose from SLOW/MODERATE/FAST.Select SLOW if the transitions follow too quickly in succession. If it takes too long beforethe control computer proceeds to another position select FAST.Delay MT->T Setting of the delay for transition from MT- to T-position. During the set time the controlcomputer will not change the exhaust at this transition.This delay does not apply with the transition from T to MT (direct control).Actual combi step Setting of the current phase in the combi-table.