Lumina 35 Explanation control functions17HumiTemp = Humidification TemperatureIf HumiTemp is used, it will correct the measured average house temperature depending on the setpoint and themeasured relative humidity (RH). If HumiTemp is not used, the ventilation is controlled based on the averagehouse temperature.Figure 6: Example HumiTempThe HumiTemp control can only activate if a humidity setpoint has been set and a humidity sensor is adjusted.The effect of the HumiTemp correction is controlled by the next settings.The age factor tells how the HumiTemp ® should adapt in relation to the age of animals. This means there is alink to the minimum ventilation. EARLY (5%) means that even at young animals the HumiTemp will reactstrongly. When this factor is NORMAL(10%) the reaction is a more gradually, and this impact is slowly with thefactor at LATE(20%).At a lower than desired RH the temperature will run down. The degree of correction is limited (safety reason). Thissetting specifies how much the compensation may decrease (related to the average house temperature) TINY (-0.5 °), SMALL (-1.0 °), average (-1.5 °), LARGE ( -2.0 °) and HUGE (-2.5 °).With a higher than desired RH the temperature will run up. The degree of correction is limited (safety reason).This setting specifies how much the compensation may increase (related to the average house temperature )TINY (1.0 °), SMALL (2.0 °), average (3.0 °), LARGE (4.0 °) and HUGE (5.0 °).