4-38 C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUALFRONT PANEL INTERFACE CHAPTER 4: INTERFACES44.2.4 LED indicators4.2.4.1 Enhanced front panelThe enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event-cause LEDs. The next four columns contain the 48 user-programmable LEDs.The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (theselatched conditions can also be reset via the SETTINGS INPUT/OUTPUTS RESETTING menu).The USER keys are used by the breaker control feature.Figure 4-47: Typical LED panel for enhanced front panelThe status indicators in the first column are as follows:• IN SERVICE — Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, andthe relay is in (online) Programmed mode (under Settings > Product Setup > Installation)RESET — Clears all latched LED indications and target messages. When a page with acknowledgeable/resettableitems is displayed, it instead resets/acknowledges all items on that page, or if an item on that page is selected, itresets/acknowledges that item.If you reset/acknowledge alarms, they stop flashing but remain in the alarm state as long as that state remains. Inother words, a red alarm does not switch off just because you acknowledged the alarm.Home — Activates the home page, which is the root page. The page displays product information by default andis configurable.Side pushbutton — Five pushbuttons on the left side of the display and five pushbuttons on the right side of thedisplay. They perform various functions depending on the displayed page, such as switchgear controls. Thedisplay dynamically shows its label next to each side pushbutton when the pushbutton has an assigned function.These pushbuttons can also be programmed to function as user-programmable pushbuttons 9 to 16.Tab pushbutton — Five pushbuttons under the display. They navigate through the page hierarchy, and on somepages activate other actions. The display footer dynamically labels the page or action that is activated by the Tabpushbutton.User-programmable pushbutton — Eight physical pushbuttons are associated with the first eight user-programmable pushbutton elements. Numbering is down, that is, 1 to 4 down the left column and 5 to 8 down theright column.These elements control a set of FlexLogic operands that can be used to initiate outputs or select modes. Eachphysical pushbutton has an integrated LED indicator that can be user-configured to display the appropriatestatus.These pushbuttons have clear covers behind which custom labels can be mounted. A utility is available to printthe labels, under File > Front Panel Report in the software.