CHAPTER 5: SETTINGS PRODUCT SETUPC60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-855Figure 5-35: Member right-clickDataSet01 nameRange: 0 to 32 VisibleString charactersDefault: DataSet01The value entered sets the name of the data set, which is required to be unique within the UR for proper operation. Thevalue entered sets the name of the data set, which is required to be unique within the UR for proper operation. Fastdatasets start with TT6, and slow datasets start with TT3. Up to six fast datasets are allowed. Up to four fast GOOSEdatasets are allowed.An ObjectReference to the data set consists of a string that is the concatenation of "/LLN0$" and theDataSet01 name setting value. An ObjectReference to the data set is published in the datSet field of TxGOOSE messages,and it can be used by subscribers to discriminate the messages of that TxGOOSE from other GOOSE messages. AnObjectReference to the data set is optionally published in the DatSet field of Report messages. Valid characters areupper and lowercase letters, digits, and the underscore (_) character. The first character must be a letter.DataSet01 shared byRange: 0 to 32 VisibleString charactersDefault:Names of all control blocks that use this DataSet. Read-only field.DataSet01 Member1Range: End of List or any instantiated 61850 data object or data attribute with Functional Constraint ST or MXDefault: End of ListThis setting specifies the first member in TxGOOSE1 messages. There is a similar setting for each of the up to 64members that the UR allows in a Dataset. Only values of members before the first set to End of List are published.Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert.Product setupNavigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup.