CHAPTER 5: SETTINGS SYSTEM SETUPC60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL 5-14955.5.4 BreakersSETTINGS SYSTEM SETUP BREAKERS BREAKER 1(4) BREAKER 1 BREAKER 1FUNCTION: DisabledRange: Disabled, Enabled BREAKER1 PUSH BUTTONCONTROL: DisabledRange: Disabled, Enabled BREAKER 1 TAGGING:DisabledRange: Disabled, Enabled BREAKER 1SUBSTITUTN: DisabledRange: Disabled, Enabled BREAKER 1 BYPASS:DisabledRange: Disabled, Enabled BREAKER 1 AR BLOCK:DisabledRange: Disabled, Enabled BREAKER 1 NAME:Bkr 1Range: up to six alphanumeric characters BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-Pole BREAKER 1 OPEN:OffRange: FlexLogic operand BREAKER 1 BLK OPEN:OffRange: FlexLogic operand BREAKER 1 CLOSE:OffRange: FlexLogic operand BREAKER 1 BLK CLOSE:OffRange: FlexLogic operand BREAKER1 ΦA/3P CLSD:OffRange: FlexLogic operand BREAKER1 ΦA/3P OPND:OffRange: FlexLogic operand BREAKER 1 ΦB CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦB OPENED:OffRange: FlexLogic operand BREAKER 1 ΦC CLOSED:OffRange: FlexLogic operand BREAKER 1 ΦC OPENED:OffRange: FlexLogic operand BREAKER 1 TOPERATE:70 msRange: 0 to 65535 s in steps of 1 BREAKER 1 EXT ALARM:OffRange: FlexLogic operand BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001 BREAKER 1 OPENSEAL-IN: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001