GE Grid Solutions D25User's ManualGE Information 994-0081-3.00-21 139CT/PT Modules, ContinuedProcedure: Metering Range Calibration(0% - 195%) (continued)Step Action8. Inject the test currents (see the following table) into the inputs, anduse the D25 AC Input Engineering Value Displays to verify that thereported raw magnitudes are within the tolerances stated in thefollowing tables:CT Type: 1A Part Number: 450-0107For Test Current… Expected Raw Value is… Tolerance1.000 Arms ± 0.05% 2048 ± 4 countsCT Type: 5A Part Number: 450-0108For Test Current… Expected Raw Value is… Tolerance1.000 Arms ± 0.05% 2048 ± 4 counts