GE Grid Solutions D25User's ManualGE Information 994-0081-3.00-21 155Electrical Specifications, ContinuedAC Current Inputs (42x Nominal)Nominal CT Input Options 1 Arms or5 ArmsDFR Range 42x nominalMeasurement Range 2% to 1600% of nominal, asymmetricalThermal Overload 4 times nominal current continuous30 times nominal current 10 seconds100 times nominal current 1 secondNote: continuous over-current may affect theaccuracy of the current values.Refer to the appropriate PRPI for the accuracyspecifications under over-current conditions.Burden Less than 0.1 VA @ nominal input currentLCD DisplayOperating temp. -20 to 70 degrees CelsiusLCD Display size 2.75” x 7.4”AC Voltage InputsNominal PT input options 63.5 V rms69.3 V rms110 V rms120 V rms220 V rmsMeasurement Range 0% to 250% of nominalOverload Voltage 250% of nominal continuous350% of nominal for one (1) minuteBurden Less than 0.1 VAAC Current Inputs (Standard)Nominal CT Input Options 1 Arms5 ArmsMeasurement and DFR Range 2% to 1600% of nominal, asymmetricalThermal Overload 4 times nominal current continuous30 times nominal current 10 seconds100 times nominal current 1 secondNote: continuous over-current may affect theaccuracy of the current values.Refer to the appropriate PRPI for the accuracyspecifications under over-current conditions.Burden Less than 0.1 VA @ nominal input current