D25User's Manual GE Grid Solutions86 994-0081-3.00-21 GE InformationTesting Hardware I/O Points, ContinuedDigital InputVerificationTestTesting Digital Inputs: Digital input changes are displayed in WESMAINT.Procedure:Verify DigitalInputTo conduct this test the code and configuration file must be downloaded tothe D25’s FLASH memory.Note: The following procedure assumes that the digital inputs for the D25are configured to use supplied wetting. Refer to page 36 forconfiguration information.From the WESMAINT II+ Main Menu:Step Action1 On the Main Menu, type 1 — System Data Display.Results: The System Data Menu appears.2 On the System Data Menu, type 1 — Digital Input Display.Results: The point numbers and (optionally) point descriptionsappear on the WESMAINT II+ display.3 Use the arrow keys to move up or down to highlight the desiredpoint number.4 Use a wire jumper to short out the desired input point, and verifythat WESMAINT shows that the point status has changed to On.5 Go back to Step 3 and repeat the test as necessary to test otheravailable digital points.Navigatingthrough screens• Press N to move to the Next page.• Press P to move to the Previous page.• Press ESC to back up to the previous menu level.