D25User's Manual GE Grid Solutions164 994-0081-3.00-21 GE InformationConnecting to Protective GroundConnect your DNP3 I/O module to site ground, using a separate 2.05 mm (12 AWG) Yellow/ Green wire.Each type of DNP I/O Module has a different ground point, as shown in theexamples below.The location of the protective ground terminal varies between WESTERM I/O module types. Refer toModule Layout drawing of your module for detailed information. For example, see below.DC Analog Input Module12 AWGGND WireSiteGround100479748 49 5098 99TB1Digital Input Module12 AWGGRN GNDSiteGround1326312964 65 66130 131TB1Control Output Module12 AWGGRN GNDSiteGround1065010351 52 53104 105TB1Combination Input OutputModuleSiteGround100479748 49 5098 99TB112 AWGGreen WireAfter site ground has been connected, you are now ready to connect power, and DNP3 link cabling to theDNP3 I/O module. See section: Connecting DNP3 I/O Modules (Low Voltage) on page 165 or section:Connecting DNP3 I/O modules (High Voltage) on page 166.