GE Grid Solutions D25User's ManualGE Information 994-0081-3.00-21 59Control Outputs, ContinuedD25KE FACE-40 CombinedR/L and T/CTrip/Close and Raise/Lower digital outputs can be used on the same D25KEFACE-40 unit.When assigning raise/lower groups, always start with group 4, then group 3,and lastly group 2.Remember that raise/lower points number in the reverse direction from otherpoint types: point 32 will become lower point 1.Note Configuring raise/lower groups with numbers lower than the trip/close groupnumbers, or between trip/close groups can result in a very complex andconfusing wiring scheme.G1 and G2Connectionsfor: 3 Groupsof Trip/Close,and One Groupof Raise/LowerJumpering is required to configure a D25KE FACE-40 module for 3 groupsof trip/close, and one group of raise/lower:Use jumper wires on the FACE-40 terminal block G1 to configure groups 1and 2.• Group 1:− connect between MTA (G1-39) and JMP1 (G1-37)• Group 2:− connect between MTA (G1-40) and JMP2 (G1-38)1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 392 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40G11 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 392 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40G2Use jumper wires on the FACE-40 terminal block G2 to configure groups 3and 4.• Group 3 for trip/close:− connect between MTB (G2-5) and JMP3 (G2-3)• Group 4 for raise/lower:− connect between VCB (G2-2) and JMP4 (G2-4)