GE Grid Solutions D25User's ManualGE Information 994-0081-3.00-21 87Testing Hardware I/O Points, ContinuedDigital OutputVerificationTestTesting Digital Outputs: You can force digital outputs from WESMAINT.!Caution!Use caution when testing digital output points that are connectedto external equipment.This test may damage external devices, such as relays orreclosers, and may injure personnel.Procedure:Verify DigitalOutputTo conduct this test the code and configuration file must be downloaded tothe D25’s FLASH memory.From the WESMAINT II+ Main Menu:Step Action1 On the Main Menu, type 1 — System Data Display.Results: The System Data Menu appears.2 On the System Data Menu, type 2 — Digital Output Display.Results: The point numbers and (optionally) point descriptionsappear on the WESMAINT II+ display.3 Use the arrow keys to move up or down to highlight the desiredpoint number.Results: The cursor should now be flashing on the specified pointnumber.4 Press CTRL+ F when you are ready to force-change the state of thedigital output point.Extra Security5 At the Password prompt, type control (*) and press ENTER .Results: The Digital Output Force Display appears.6 Press CTRL+U to change (update) the relay state.