GE Multilin F60 Feeder Protection System 4-174 HUMAN INTERFACES 4.2 FACEPLATE INTERFACE4• GROUP 1...6: The illuminated GROUP is the active settings group.• BREAKER 1(2) OPEN: The breaker is open.• BREAKER 1(2) CLOSED: The breaker is closed.• BREAKER 1(2) TROUBLE: A problem related to the breaker has been detected.• SYNCHROCHECK NO1(2) IN-SYNCH: Voltages have satisfied the synchrocheck element.• RECLOSE ENABLED: The recloser is operational.• RECLOSE DISABLED: The recloser is not operational.• RECLOSE IN PROGRESS: A reclose operation is in progress.• RECLOSE LOCKED OUT: The recloser is not operational and requires a reset.Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six settinggroups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups.Please note that the LEDs, despite their default labels, are fully user-programmable.The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match thepre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. TheLEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explainedin the following section.Figure 4–21: LED PANEL 2 (DEFAULT LABELS)4.2.3 CUSTOM LABELING OF LEDSa) ENHANCED FACEPLATEThe following procedure requires these pre-requisites:• EnerVista UR Setup software is installed and operational• The F60 settings have been saved to a settings file• The F60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded fromhttp://www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc and printed• Small-bladed knifeTo create custom LED labels for the enhanced front panel display:1. Start the EnerVista UR Setup software.NOTE842784A1.CDR