GE Multilin F60 Feeder Protection System 5-1375 SETTINGS 5.5 FLEXLOGIC5The operands available for this relay are listed alphabetically by types in the following table.Table 5–14: F60 FLEXLOGIC OPERANDS (Sheet 1 of 9)OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTIONCONTROLPUSHBUTTONSCONTROL PUSHBTN 1 ONCONTROL PUSHBTN 2 ONCONTROL PUSHBTN 3 ONCONTROL PUSHBTN 4 ONCONTROL PUSHBTN 5 ONCONTROL PUSHBTN 6 ONCONTROL PUSHBTN 7 ONControl pushbutton 1 is being pressedControl pushbutton 2 is being pressedControl pushbutton 3 is being pressedControl pushbutton 4 is being pressedControl pushbutton 5 is being pressedControl pushbutton 6 is being pressedControl pushbutton 7 is being pressedDIRECT DEVICES DIRECT DEVICE 1OnDIRECT DEVICE 16OnDIRECT DEVICE 1OffDIRECT DEVICE 16OffFlag is set, logic=1Flag is set, logic=1Flag is set, logic=1Flag is set, logic=1DIRECT INPUT/OUTPUTCHANNELMONITORINGDIR IO CH1 CRC ALARMDIR IO CH2 CRC ALARMDIR IO CH1 UNRET ALMDIR IO CH2 UNRET ALMThe rate of direct input messages received on channel 1 and failing the CRCexceeded the user-specified level.The rate of direct input messages received on channel 2 and failing the CRCexceeded the user-specified level.The rate of returned direct input/output messages on channel 1 exceeded theuser-specified level (ring configurations only).The rate of returned direct input/output messages on channel 2 exceeded theuser-specified level (ring configurations only).ELEMENT:Autoreclose(per CT bank)AR1 ENABLEDAR1 RIPAR1 LOAR1 BLK FROM MAN CLSAR1 CLOSEAR1 SHOT CNT=0AR1 SHOT CNT=1AR1 SHOT CNT=2AR1 SHOT CNT=3AR1 SHOT CNT=4AR1 DISABLEDAutoreclose 1 is enabledAutoreclose 1 is in progressAutoreclose 1 is locked outAutoreclose 1 is temporarily disabledAutoreclose 1 close command is issuedAutoreclose 1 shot count is 0Autoreclose 1 shot count is 1Autoreclose 1 shot count is 2Autoreclose 1 shot count is 3Autoreclose 1 shot count is 4Autoreclose 1 is disabledELEMENT:AuxiliaryovervoltageAUX OV1 PKPAUX OV1 DPOAUX OV1 OPAuxiliary overvoltage element has picked upAuxiliary overvoltage element has dropped outAuxiliary overvoltage element has operatedAUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1ELEMENT:AuxiliaryundervoltageAUX UV1 PKPAUX UV1 DPOAUX UV1 OPAuxiliary undervoltage element has picked upAuxiliary undervoltage element has dropped outAuxiliary undervoltage element has operatedAUX UV2 to AUX UV3 Same set of operands as shown for AUX UV1ELEMENTBreaker flashoverBKR 1 FLSHOVR PKP ABKR 1 FLSHOVR PKP BBKR 1 FLSHOVR PKP CBKR 1 FLSHOVR PKPBKR 1 FLSHOVR OP ABKR 1 FLSHOVR OP BBKR 1 FLSHOVR OP CBKR 1 FLSHOVR OPBKR 1 FLSHOVR DPO ABKR 1 FLSHOVR DPO BBKR 1 FLSHOVR DPO CBKR 1 FLSHOVR DPOBreaker 1 flashover element phase A has picked upBreaker 1 flashover element phase B has picked upBreaker 1 flashover element phase C has picked upBreaker 1 flashover element has picked upBreaker 1 flashover element phase A has operatedBreaker 1 flashover element phase B has operatedBreaker 1 flashover element phase C has operatedBreaker 1 flashover element has operatedBreaker 1 flashover element phase A has dropped outBreaker 1 flashover element phase B has dropped outBreaker 1 flashover element phase C has dropped outBreaker 1 flashover element has dropped outBKR 2 FLSHOVR... Same set of operands as shown for BKR 1 FLSHOVRELEMENT:Breaker arcing BKR ARC 1 OPBKR ARC 2 OP Breaker arcing current 1 has operatedBreaker arcing current 2 has operatedELEMENTBreaker failure BKR FAIL 1 RETRIPABKR FAIL 1 RETRIPBBKR FAIL 1 RETRIPCBKR FAIL 1 RETRIPBKR FAIL 1 T1 OPBKR FAIL 1 T2 OPBKR FAIL 1 T3 OPBKR FAIL 1 TRIP OPBreaker failure 1 re-trip phase A (only for 1-pole schemes)Breaker failure 1 re-trip phase B (only for 1-pole schemes)Breaker failure 1 re-trip phase C (only for 1-pole schemes)Breaker failure 1 re-trip 3-phaseBreaker failure 1 timer 1 is operatedBreaker failure 1 timer 2 is operatedBreaker failure 1 timer 3 is operatedBreaker failure 1 trip is operatedBKR FAIL 2... Same set of operands as shown for BKR FAIL 1