GE Multilin F60 Feeder Protection System C-25APPENDIX C C.6 ACSI CONFORMANCECc6: shall declare support for at least one (BRCB or URCB)c7: shall declare support for at least one (QueryLogByTime or QueryLogAfter)c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)c9: shall declare support if TP association is availablec10: shall declare support for at least one (SendMSVMessage or SendUSVMessage)S44 SetGsCBValues TP O YesTRANSMISSION OF SAMPLED VALUE MODEL (SVC) (CLAUSE 19)MULTICAST SVCS45 SendMSVMessage MC c10S46 GetMSVCBValues TP OS47 SetMSVCBValues TP OUNICAST SVCS48 SendUSVMessage MC c10S49 GetUSVCBValues TP OS50 SetUSVCBValues TP OCONTROL (CLAUSE 20)S51 Select O YesS52 SelectWithValue TP OS53 Cancel TP O YesS54 Operate TP M YesS55 Command-Termination TP OS56 TimeActivated-Operate TP OFILE TRANSFER (CLAUSE 23)S57 GetFile TP M YesS58 SetFile TP OS59 DeleteFile TP OS60 GetFileAttributeValues TP M YesTIME (CLAUSE 5.5)T1 Time resolution of internal clock(nearest negative power of 2 inseconds)20T2 Time accuracy of internal clock SNTP, IRIG-BT3 Supported TimeStamp resolution(nearest value of 2 –n in seconds,according to 6.1.2.9.3.2)20SERVICES AA: TP/MC SERVER/PUBLISHERUR FAMILYNOTE