B-44 F60 Feeder Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BB7916 PMU TCP port number 1 to 65535 --- 1 F001 47127917 PMU UDP port number 1 1 to 65535 --- 1 F001 47137918 PMU UDP port number 2 1 to 65535 --- 1 F001 4714Phasor Measurement Unit Calibration (Read/Write Setting) (4 modules)7919 PMU Va Calibration Angle -5 to 5 ° 0.05 F002 0791A PMU Va Calibration Magnitude 95 to 105 % 0.1 F002 1000791B PMU Vb Calibration Angle -5 to 5 ° 0.05 F002 0791C PMU Vb Calibration Magnitude 95 to 105 % 0.1 F002 1000791D PMU Vc Calibration Angle -5 to 5 ° 0.05 F002 0791E PMU Vc Calibration Magnitude 95 to 105 % 0.1 F002 1000791F PMU Vx Calibration Angle -5 to 5 ° 0.05 F002 07920 PMU Vx Calibration Magnitude 95 to 105 % 0.1 F002 10007921 PMU Ia Calibration Angle -5 to 5 ° 0.05 F002 07922 PMU Ia Calibration Magnitude 95 to 105 % 0.1 F002 10007923 PMU Ib Calibration Angle -5 to 5 ° 0.05 F002 07924 PMU Ib Calibration Magnitude 95 to 105 % 0.1 F002 10007925 PMU Ic Calibration Angle -5 to 5 ° 0.05 F002 07926 PMU Ic Calibration Magnitude 95 to 105 % 0.1 F002 10007927 PMU Ig Calibration Angle -5 to 5 ° 0.05 F002 07928 PMU Ig Calibration Magnitude 95 to 105 % 0.1 F002 10007929 PMU Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0792A PMU Sequence Current Shift Angle -180 to 180 ° 30 F002 0Phasor Measurement Unit Triggering (Read/Write Setting) (4 modules)7970 PMU 1 User Trigger 0 to 4294967295 --- 1 F300 0Phasor Measurement Unit Current Trigger (Read/Write Setting) (4 modules)7980 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)7981 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 18007982 PMU 1 Current Trigger Pickup Time 0 to 600 s 0.01 F001 107983 PMU 1 Current Trigger Dropout Time 0 to 600 s 0.01 F001 1007984 PMU 1 Current Trigger Block (3 items) 0 to 4294967295 --- 1 F300 0798A PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)798B PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)Phasor Measurement Unit df/dt Trigger (Read/Write Setting)79B0 PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)79B1 PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 2579B2 PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 2579B3 PMU 1 df/dt Trigger Pickup Time 0 to 600 s 0.01 F001 1079B4 PMU 1 df/dt Trigger Dropout Time 0 to 600 s 0.01 F001 10079B5 PMU 1 df/dt Trigger Block (3 items) 0 to 4294967295 --- 1 F300 079BB PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)79BC PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)High Impedance Fault Detection (Hi-Z) Settings (Read/Write Setting)7A00 Hi-Z Function 0 to 1 --- 1 F102 0 (Disabled)7A01 Hi-Z Signal Source 0 to 5 --- 1 F167 0 (SRC 1)7A03 Hi-Z Arcing Sensitivity 1 to 10 --- 1 F001 57A04 Hi-Z Phase Event Count 10 to 250 --- 1 F001 307A05 Hi-Z Ground Event Count 10 to 500 --- 1 F001 307A06 Hi-Z Event Count Time 5 to 180 min 1 F001 157A07 Hi-Z Overcurrent Protection Coordination Timeout 10 to 200 s 1 F001 157A08 Hi-Z Phase Overcurrent Minimum Pickup 0.01 to 10 pu 0.01 F001 1507A09 Hi-Z Neutral Overcurrent Minimum Pickup 0.01 to 10 pu 0.01 F001 1007A0A Hi-Z Phase Rate of Change 1 to 999 A/2cycle 1 F001 1507A0B Hi-Z Neutral Rate of Change 1 to 999 A/2cycle 1 F001 1507A0C Hi-Z Loss of Load Threshold 5 to 100 % 1 F001 15Table B–9: MODBUS MEMORY MAP (Sheet 36 of 68)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT