5-28 G60 Generator Management Relay GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.5.2.11 USER-PROGRAMMABLE SELF TESTSPATH: SETTINGS ! PRODUCT SETUP !" USER-PROGRAMMABLE SELF TESTSAll major self-test alarms are reported automatically with their corresponding FlexLogicô operands, events, and targets.Most of the Minor Alarms can be disabled if desired.When in the ìDisabledî mode, minor alarms will not assert a FlexLogicô operand, write to the event recorder, display targetmessages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the ìEnabledî mode,minor alarms continue to function along with other major and minor alarms. Refer to the Relay Self-Tests section in Chapter7 for additional information on major and minor self-test alarms.Table 5ñ2: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELSSETTING PARAMETER SETTING PARAMETERLED 1 Operand SETTING GROUP ACT 1 LED 13 Operand OffLED 2 Operand SETTING GROUP ACT 2 LED 14 Operand OffLED 3 Operand SETTING GROUP ACT 3 LED 15 Operand OffLED 4 Operand SETTING GROUP ACT 4 LED 16 Operand OffLED 5 Operand SETTING GROUP ACT 5 LED 17 Operand SYNC 1 SYNC OPLED 6 Operand SETTING GROUP ACT 6 LED 18 Operand SYNC 2 SYNC OPLED 7 Operand Off LED 19 Operand OffLED 8 Operand Off LED 20 Operand OffLED 9 Operand Off LED 21 Operand OffLED 10 Operand Off LED 22 Operand OffLED 11 Operand Off LED 23 Operand OffLED 12 Operand Off LED 24 Operand Off# USER-PROGRAMMABLE# SELF TESTSDIRECT RING BREAKFUNCTION: EnabledRange: Disabled, Enabled.Valid for units equipped with Direct I/O Module.MESSAGE DIRECT DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled.Valid for units equipped with Direct I/O Module.MESSAGE REMOTE DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled.Valid for units equipped with CPU Type C or D.MESSAGE PRI. ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.Valid for units equipped with CPU Type C or D.MESSAGE SEC. ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.Valid for units equipped with CPU Type D.MESSAGE BATTERY FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE SNTP FAILFUNCTION: EnabledRange: Disabled, Enabled.Valid for units equipped with CPU Type C or D.MESSAGE IRIG-B FAILFUNCTION: EnabledRange: Disabled, Enabled.