5-78 G60 Generator Management Relay GE Multilin5.5 GROUPED ELEMENTS 5 SETTINGS55.5.4 POWER SWING DETECTPATH: SETTINGS !" GROUPED ELEMENTS ! SETTING GROUP 1(6) !" POWER SWING DETECT# POWER SWING# DETECTPOWER SWINGFUNCTION: DisabledRange: Disabled, EnabledMESSAGE POWER SWINGSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE POWER SWINGSHAPE: Mho ShapeRange: Mho Shape, Quad ShapeMESSAGE POWER SWINGMODE: Two StepRange: Two Step, Three StepMESSAGE POWER SWINGSUPV: 0.600 puRange: 0.050 to 30.000 pu in steps of 0.001MESSAGE POWER SWING FWDREACH: 50.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING QUAD FWDREACH MID: 60.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING QUAD FWDREACH OUT: 70.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING FWDRCA: 75∞Range: 40 to 90∞ in steps of 1MESSAGE POWER SWING REVREACH: 50.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING QUAD REVREACH MID: 60.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING QUAD REVREACH OUT: 70.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING REVRCA: 75∞Range: 40 to 90∞ in steps of 1MESSAGE POWER SWING OUTERLIMIT ANGLE: 120∞Range: 40 to 140∞ in steps of 1MESSAGE POWER SWING MIDDLELIMIT ANGLE: 90∞Range: 40 to 140∞ in steps of 1MESSAGE POWER SWING INNERLIMIT ANGLE: 60∞Range: 40 to 140∞ in steps of 1MESSAGE POWER SWING OUTERRGT BLD: 100.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING OUTERLFT BLD: 100.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING MIDDLERGT BLD: 100.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING MIDDLELFT BLD: 100.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01MESSAGE POWER SWING INNERRGT BLD: 100.00 ΩRange: 0.10 to 500.00Ω in steps of 0.01