5-10 G60 Generator Management Relay GE Multilin5.2 PRODUCT SETUP 5 SETTINGS55.2.3 CLEAR RELAY RECORDSPATH: SETTINGS ! PRODUCT SETUP !" CLEAR RELAY RECORDSSelected records can be cleared from user-programmable conditions with FlexLogicô operands. Assigning user-program-mable pushbuttons to clear specific records are typical applications for these commands. Since the G60 responds to risingedges of the configured FlexLogicô operands, they must be asserted for at least 50 ms to take effect.Clearing records with user-programmable operands is not protected by the command password. However, user-program-mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-ble pushbuttons can provide extra security if required.For example, to assign User-Programmable Pushbutton 1 to clear demand records, the following settings should beapplied.1. Assign the clear demand function to Pushbutton 1 by making the following change in the SETTINGS ! PRODUCT SETUP!" CLEAR RELAY RECORDS menu:CLEAR DEMAND: ì PUSHBUTTON 1 ON î2. Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS ! PRODUCTSETUP !" USER-PROGRAMMABLE PUSHBUTTONS ! USER PUSHBUTTON 1 menu:PUSHBUTTON 1 FUNCTION: ìSelf-resetîPUSHBTN 1 DROP-OUT TIME: ì0.20 sî# CLEAR RELAY# RECORDSCLEAR USER REPORTS:OffRange: FlexLogicô operandMESSAGE CLEAR EVENT RECORDS:OffRange: FlexLogicô operandMESSAGE CLEAR OSCILLOGRAPHY?NoRange: FlexLogicô operandMESSAGE CLEAR DATA LOGGER:OffRange: FlexLogicô operandMESSAGE CLEAR ENERGY:OffRange: FlexLogicô operandMESSAGE RESET UNAUTH ACCESS:OffRange: FlexLogicô operandMESSAGE CLEAR DIR I/O STATS:OffRange: FlexLogicô operand.Valid only for units with Direct I/O module.