GE Multilin G60 Generator Management Relay 5-1695 SETTINGS 5.7 INPUTS/OUTPUTS5Write the following FlexLogicô equation (EnerVista UR Setup example shown):Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.Program the Latching Outputs by making the following changes in the SETTINGS !" INPUTS/OUTPUT !" CONTACT OUT-PUTS ! CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):OUTPUT H1a OPERATE: ì VO1 î OUTPUT H1c OPERATE: ì VO2 îOUTPUT H1a RESET: ì VO4 î OUTPUT H1c RESET: ì VO3 îApplication Example 4:A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1is high, and should stay opened when VO1 is low. Program the relay as follows.Write the following FlexLogicô equation (EnerVista UR Setup example shown):Program the Latching Outputs by making the following changes in the SETTINGS !" INPUTS/OUTPUT !" CONTACT OUT-PUTS ! CONTACT OUTPUT H1a menu (assuming an H4L module):OUTPUT H1a OPERATE: ì VO1 îOUTPUT H1a RESET: ì VO2 î5.7.4 VIRTUAL OUTPUTSPATH: SETTINGS !" INPUTS/OUTPUTS !" VIRTUAL OUTPUTS ! VIRTUAL OUTPUT 1(64)There are 64 virtual outputs that may be assigned via FlexLogicô. If not assigned, the output will be forced to ëOFFí (Logic0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of theFlexLogicô equations. Any change of state of a virtual output can be logged as an event if programmed to do so.For example, if Virtual Output 1 is the trip signal from FlexLogicô and the trip relay is used to signal events, the settingswould be programmed as follows:VIRTUAL OUTPUT 1 ID: "Trip"VIRTUAL OUTPUT 1 EVENTS: "Disabled"# VIRTUAL OUTPUT 1#VIRTUAL OUTPUT 1 IDVirt Op 1Range: Up to 12 alphanumeric charactersMESSAGE VIRTUAL OUTPUT 1EVENTS: DisabledRange: Disabled, Enabled