GE Multilin G60 Generator Management Relay 5-115 SETTINGS 5.2 PRODUCT SETUP55.2.4 COMMUNICATIONSa) MAIN MENUPATH: SETTINGS ! PRODUCT SETUP !" COMMUNICATIONSb) SERIAL PORTSPATH: SETTINGS ! PRODUCT SETUP !" COMMUNICATIONS ! SERIAL PORTSThe G60 is equipped with up to 3 independent serial communication ports. The faceplate RS232 port is intended for localuse and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet orRS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important thatthese parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any ofthese ports may be connected to a computer running EnerVista UR Setup. This software can download and upload settingfiles, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and con-nected to a DCS, PLC or PC using the RS485 ports.# COMMUNICATIONS## SERIAL PORTS# See below.MESSAGE # NETWORK# See page 5ñ12.MESSAGE # MODBUS PROTOCOL# See page 5ñ12.MESSAGE # DNP PROTOCOL# See page 5ñ13.MESSAGE # IEC 61850 PROTOCOL# See page 5ñ15.MESSAGE # WEB SERVER# HTTP PROTOCOL See page 5ñ17.MESSAGE # TFTP PROTOCOL# See page 5ñ18.MESSAGE # IEC 60870-5-104# PROTOCOL See page 5ñ18.MESSAGE # SNTP PROTOCOL# See page 5ñ19.MESSAGE # EGD PROTOCOL# See page 5ñ19.# SERIAL PORTS#RS485 COM1 BAUDRATE: 19200Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,28800, 33600, 38400, 57600, 115200. Onlyactive if CPU 9E is ordered.MESSAGE RS485 COM1 PARITY:NoneRange: None, Odd, EvenOnly active if CPU Type 9E is orderedMESSAGE RS485 COM1 RESPONSEMIN TIME: 0 msRange: 0 to 1000 ms in steps of 10Only active if CPU Type 9E is orderedMESSAGE RS485 COM2 BAUDRATE: 19200Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,28800, 33600, 38400, 57600, 115200MESSAGE RS485 COM2 PARITY:NoneRange: None, Odd, EvenMESSAGE RS485 COM2 RESPONSEMIN TIME: 0 msRange: 0 to 1000 ms in steps of 10