GE Multilin G60 Generator Management Relay C-7APPENDIX C C.3 LOGICAL NODESCC.3LOGICAL NODES C.3.1 LOGICAL NODES TABLEThe UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-tion of each logical node is determined by the product order code. For example. the logical node ìPDISî (distance protec-tion) is available only in the D60 Line Distance Relay.NODES UR-FAMILYL: SYSTEM LOGICAL NODESLPHD: Physical device information YesLLN0: Logical node zero YesP: LOGICAL NODES FOR PROTECTION FUNCTIONSPDIF: Differential ---PDIR: Direction comparison ---PDIS: Distance YesPDOP: Directional overpower ---PDUP: Directional underpower ---PFRC: Rate of change of frequency ---PHAR: Harmonic restraint ---PHIZ: Ground detector ---PIOC: Instantaneous overcurrent YesPMRI Motor restart inhibition ---PMSS: Motor starting time supervision ---POPF: Over power factor ---PPAM: Phase angle measuring ---PSCH: Protection scheme ---PSDE: Sensitive directional earth fault ---PTEF: Transient earth fault ---PTOC: Time overcurrent YesPTOF: Overfrequency ---PTOV: Overvoltage YesPTRC: Protection trip conditioning YesPTTR: Thermal overload YesPTUC: Undercurrent ---PTUV: Undervoltage YesPUPF: Underpower factor ---PTUF: Underfrequency ---PVOC: Voltage controlled time overcurrent ---PVPH: Volts per Hz ---PZSU: Zero speed or underspeed ---R: LOGICAL NODES FOR PROTECTION RELATEDFUNCTIONSRDRE: Disturbance recorder function ---RADR: Disturbance recorder channel analogue ---RBDR: Disturbance recorder channel binary ---RDRS: Disturbance record handling ---RBRF: Breaker failure YesRDIR: Directional element ---RFLO: Fault locator YesRPSB: Power swing detection/blocking YesRREC: Autoreclosing YesRSYN: Synchronism-check or synchronizing ---C: LOGICAL NODES FOR CONTROLCALH: Alarm handling ---CCGR: Cooling group control ---CILO: Interlocking ---CPOW: Point-on-wave switching ---CSWI: Switch controller ---G: LOGICAL NODES FOR GENERIC REFERENCESGAPC: Generic automatic process control ---GGIO: Generic process I/O YesGSAL: Generic security application ---I: LOGICAL NODES FOR INTERFACING AND ARCHIVINGIARC: Archiving ---IHMI: Human machine interface ---ITCI: Telecontrol interface ---ITMI: Telemonitoring interface ---A: LOGICAL NODES FOR AUTOMATIC CONTROLANCR: Neutral current regulator ---ARCO: Reactive power control ---ATCC: Automatic tap changer controller ---AVCO: Voltage control ---M: LOGICAL NODES FOR METERING AND MEASUREMENTMDIF: Differential measurements ---MHAI: Harmonics or interharmonics ---MHAN: Non phase related harmonics orinterharmonic---MMTR: Metering ---MMXN: Non phase related measurement ---MMXU: Measurement YesMSQI: Sequence and imbalance ---MSTA: Metering statistics ---S: LOGICAL NODES FOR SENSORS AND MONITORINGSARC: Monitoring and diagnostics for arcs ---SIMG: Insulation medium supervision (gas) ---SIML: Insulation medium supervision (liquid) ---SPDC: Monitoring and diagnostics for partialdischarges ---X: LOGICAL NODES FOR SWITCHGEARXCBR: Circuit breaker YesXSWI: Circuit switch ---T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERSTCTR: Current transformer ---TVTR: Voltage transformer ---NODES UR-FAMILY