2-12 G60 Generator Management Relay GE Multilin2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION22.2.7 OUTPUTSFORM-A RELAYMake and carry for 0.2 s: 30 A as per ANSI C37.90Carry continuous: 6 ABreak at L/R of 40 ms: 0.25 A DC max. at 48 V0.10 A DC max. at 125 VOperate time: < 4 msContact material: Silver alloyLATCHING RELAYMake and carry for 0.2 s: 30 A as per ANSI C37.90Carry continuous: 6 ABreak at L/R of 40 ms: 0.25 A DC max.Operate time: < 4 msContact material: Silver alloyControl: separate operate and reset inputsControl mode: operate-dominant or reset-dominantFORM-A VOLTAGE MONITORApplicable voltage: approx. 15 to 250 V DCTrickle current: approx. 1 to 2.5 mAFORM-A CURRENT MONITORThreshold current: approx. 80 to 100 mAFORM-C AND CRITICAL FAILURE RELAYMake and carry for 0.2 s: 10 ACarry continuous: 6 ABreak at L/R of 40 ms: 0.25 A DC max. at 48 V0.10 A DC max. at 125 VOperate time: < 8 msContact material: Silver alloyFAST FORM-C RELAYMake and carry: 0.1 A max. (resistive load)Minimum load impedance:Operate time: < 0.6 msInternal Limiting Resistor: 100 Ω, 2 WSOLID-STATE OUTPUT RELAYOperate and release time: <100 μsMaximum voltage: 265 V DCMaximum continuous current: 5 A at 45∞C; 4 A at 65∞CMake and carry for 0.2 s: as per ANSI C37.90Breaking capacity:IRIG-B OUTPUTAmplitude: 10 V peak-peak RS485 levelMaximum load: 100 ohmsTime delay: 1 ms for AM input40 μs for DC-shift inputIsolation: 2 kVCONTROL POWER EXTERNAL OUTPUT(FOR DRY CONTACT INPUT)Capacity: 100 mA DC at 48 V DCIsolation: ±300 VpkREMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)Standard output points: 32User output points: 32DIRECT OUTPUTSOutput points: 32DCMA OUTPUTSRange: ñ1 to 1 mA, 0 to 1 mA, 4 to 20 mAMax. load resistance: 12 kΩ for ñ1 to 1 mA range12 kΩ for 0 to 1 mA range600 Ω for 4 to 20 mA rangeAccuracy: ±0.75% of full-scale for 0 to 1 mA range±0.5% of full-scale for ñ1 to 1 mA range±0.75% of full-scale for 0 to 20 mA range99% Settling time to a step change: 100 msIsolation: 1.5 kVDriving signal: any FlexAnalog quantityUpper and lower limit for the driving signal: ñ90 to 90 pu in steps of0.001INPUTVOLTAGE IMPEDANCE2 W RESISTOR 1 W RESISTOR250 V DC 20 KΩ 50 KΩ120 V DC 5 KΩ 2 KΩ48 V DC 2 KΩ 2 KΩ24 V DC 2 KΩ 2 KΩNote: values for 24 V and 48 V are the same due to arequired 95% voltage drop across the load impedance.IEC 647-5 / UL508 Utilityapplication(autoreclosescheme)IndustrialapplicationOperations/interval 5000 ops /1 s-On, 9 s-Off5 ops /0.2 s-On,0.2 s-Offwithin 1minute10000 ops /0.2 s-On,30 s-Off1000 ops /0.5 s-On, 0.5 s-OffBreakcapability(0 to 250 VDC)3.2 AL/R = 10 ms10 AL/R = 40 ms 10 AL/R = 40 ms1.6 AL/R = 20 ms0.8 AL/R = 40 ms