6-4 G60 Generator Management Relay GE Multilin6.2 STATUS 6 ACTUAL VALUES66.2.4 CONTACT OUTPUTSPATH: ACTUAL VALUES ! STATUS !" CONTACT OUTPUTSThe present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contactoutput. For example, ëCont Op 1í refers to the contact output in terms of the default name-array index. The second line ofthe display indicates the logic state of the contact output.For Form-A outputs, the state of the voltage(V) and/or current(I) detectors will show as: Off, VOff, IOff, On,VOn, and/or IOn. For Form-C outputs, the state will show as Off or On.6.2.5 VIRTUAL OUTPUTSPATH: ACTUAL VALUES ! STATUS !" VIRTUAL OUTPUTSThe present state of up to 64 virtual outputs is shown here. The first line of a message display indicates the ID of the virtualoutput. For example, ëVirt Op 1í refers to the virtual output in terms of the default name-array index. The second line of thedisplay indicates the logic state of the virtual output, as calculated by the FlexLogicô equation for that output.6.2.6 REMOTE DEVICESa) STATUSPATH: ACTUAL VALUES ! STATUS !" REMOTE DEVICES STATUSThe present state of up to 16 programmed Remote Devices is shown here. The ALL REMOTE DEVICES ONLINE message indi-cates whether or not all programmed Remote Devices are online. If the corresponding state is "No", then at least onerequired Remote Device is not online.# CONTACT OUTPUTS#Cont Op 1Off↓MESSAGE Cont Op xxOff# VIRTUAL OUTPUTS#Virt Op 1Off↓MESSAGE Virt Op 64Off# REMOTE DEVICES# STATUSAll REMOTE DEVICESONLINE: NoRange: Yes, NoMESSAGE REMOTE DEVICE 1STATUS: OfflineRange: Online, Offline↓MESSAGE REMOTE DEVICE 16STATUS: OfflineRange: Online, OfflineNOTE