Addressable Modules 6\VWHP 2YHUYLHZAFP-300/AFP-400 Installation PN 50253:C1 05/22/97 1-13$GGUHVVDEOH0RGXOHV2YHUYLHZCMX Series Control Modules and MMX Series Monitor Modules provide an interfacebetween the control panel and conventional notification (CMX) and initiating (MMX)devices. You can set each CMX and MMX module to respond to an address with built-in rotary decimal switches. A blinking LED on an MMX or CMX indicatescommunication between the module and the control panel.0RGXOH'HVFULSWLRQVTable 1-9 contains description of CMX and MMX series modules and other addressablemodules used with the control panel:Table 1-9 Addressable ModulesOption DescriptionMonitor Modules(MMX-1, MMX-2)Addressable Monitor Modules for monitoring conventionalinitiating devices. The MMX-1 is used for normally opencontact alarm initiating devices, such as manual pull stations,four-wire smoke detectors, heat detectors, waterflow, securitycontacts, and supervisory devices. Use the MMX-2 forspecific two-wire smoke detectors in addition to normallyopen contacts. Wire supervised circuits as NFPA Style B orStyle D circuits.MMX-101 An Addressable Module that is functionally similar to anMMX-1 Monitor Module (Style B circuits only), but offeredin a smaller package for mounting directly in the electricalbox of the device being monitored. It does not include ablinking LED or a magnetic test switch.Control Modules(CMX)Addressable Control Modules used as Notification ApplianceCircuits (NACs) to power and supervise compatible,UL-listed notification appliances. Wire supervised circuits asNFPA Style Y or Style Z. Breaking the two built-in tabsallows using the CMX as a Form-C control relay. A CMXcomes with a thermoplastic cover for mounting to a 4-inchsquare mounting box.Loop Isolator Module(ISO-X))The ISO-X is an automatic switch that opens the circuitvoltage to a communications loop branch(es) whenever a faultis detected on that circuit. The remainder of thecommunications loop leading up to the ISO-X continues tooperate, unaffected by the fault.BGX-101L) A dual action addressable manual pull station featuring akey-lock reset. The pull station includes an MMX-101 andresponds to an address set with built-in rotary decimalswitches.www.PDF-Zoo.com