18 Device Description WAGO-I/O-SYSTEM 750750-494 3-Phase Power Measurement ModuleManualVersion 1.2.0Pos : 35 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üss e/CAGE CLAMP- Anschl üss e - Ü berschrift 3 @ 6\mod_1256296337770_21.doc x @ 43674 @ 3 @ 13.2.3 CAGE CLAMP® ConnectorsPos : 36 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üss e/Analogei ngangs klemmen/Ansc hlüsse 750-0493,- 0494 CAGE CLAMP @ 14\mod_1363951572599_21.doc x @ 115752 @ @ 18 CAGE CLAMP ® connectors make up the measuring inputs. The 3-phase supplynetwork and the loads are clamped here. See also section “Connect Devices“.Two connectors each form the three measuring channels:• L1 and IL1: voltage and current of phase L1• L2 and IL2: voltage and current of phase L2• L3 and IL3: voltage and current of phase L3Figure 3: CAGE CLAMP ® ConnectorsTable 6: Legend for Figure “CAGE CLAMP ® Connectors”Channel Designation Connector Function1 L1 1 Voltage L1IL1 5 Current L12 L2 2 Voltage L2IL2 6 Current L23 L3 3 Voltage L3IL3 7 Current L3−N 4 Neutral wire forvoltage measurementIN 8 Neutral wire forcurrent measurementPos : 37 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1