44 Process Image WAGO-I/O-SYSTEM 750750-494 3-Phase Power Measurement ModuleManualVersion 1.2.0OVER_2 Range limiting for process value 2:0 = Ok1 = The measured value shown in process value 2is situated outside the defined value range.OVER_3 Range limiting for process value 3:0 = Ok1 = The measured value shown in process value 3is situated outside the defined value range.OVER_4 Range limiting for process value 4:0 = Ok1 = The measured value shown in process value 4is situated outside the defined value range.STAT_SEL Confirmation for the status query requested in the output data– Status active for:0 = Status Phase L11 = Status Phase L22 = Status Phase L33 = Status I/O moduleExpanded status word 1Byte 2(Bit 7) (Bit 6) (Bit 5) (Bit 4) (Bit 3) (Bit 2) (Bit 1) (Bit 0)STAT7 STAT6 STAT5 STAT4 STAT3 STAT2 STAT1 -STAT7 STAT_SEL = Status Lx = L1 / L2 / L3:- Threshold value Undervoltage Lx:0 = Threshold not reached1 = Threshold reached or exceededSTAT_SEL = Status I/O module:No significanceSTAT6 STAT_SEL = Status Lx = L1 / L2 / L3:- Threshold value Overvoltage Lx:0 = Threshold not reached1 = Threshold reached or exceededSTAT_SEL = Status I/O module:Rotating Field Indicator0 = Rotary field correct L1-L2-L3, clockwise1 = Rotary field not correct, counter-clockwiseSTAT5 STAT_SEL = Status Lx = L1 / L2 / L3:- Threshold value Overcurrent Lx:0 = Threshold not reached1 = Threshold reached or exceededSTAT_SEL = Status I/O module:No significance