WAGO-I/O-SYSTEM 750 Process Image 45750-494 3-Phase Power Measurement ModuleManualVersion 1.2.0STAT4 STAT_SEL = Status Lx = L1 / L2 / L3:- Status Zero crossings:0 = Signal zero crossings at the phase Lx1 = No signal zero crossings at the phase LxSTAT_SEL = Status I/O module:No significanceSTAT3 STAT_SEL = Status Lx = L1 / L2 / L3:- Clipping of voltage signal at Lx:0 = OK1 = The voltage signal is outside the measurablerange of the I/O module and has beenlimited (clipped).STAT_SEL = Status I/O module:No significanceSTAT2 STAT_SEL = Status Lx = L1 / L2 / L3:- Clipping of current signal at Lx:0 = OK1 = The current signal is outside the measurablerange of the I/O module and has beenlimited (clipped).STAT_SEL = Status I/O module:No significanceSTAT1 STAT_SEL = Status Lx = L1 / L2 / L3:- SagLevel Voltage Lx:0 = OK1 = Elevated measuring error due to inadequateinput voltage at LxSTAT_SEL = Status I/O module:No significanceByte 3(Bit 7) (Bit 6) (Bit 5) (Bit 4) (Bit 3) (Bit 2) (Bit 1) (Bit 0)COL_ID_SELCOL_ID_SEL Index for the selected measured value collection (see alsoCOL_ID in output data):000 … 006= reserved007 = DC measured values008 = reserved009 = AC measured values010 … 019= reserved020 = Harmonics analysis L1021 = Harmonics analysis L2022 = Harmonics analysis L3023 … 255= reserved