50 Process Image WAGO-I/O-SYSTEM 750750-494 3-Phase Power Measurement ModuleManualVersion 1.2.0The I/O module measured values are made available in the process image as afunction of the selected collection (COL_ID) and of the measured values selectedin the collection.Collections DC (007) and AC measured values (009)The collection is selected in the I/O module output data and the various measuredvalues selected from the collection using the corresponding MET_IDs. Thesemeasured values are then made available in the input data. After this, four otherMET_IDs can be selected, and so on.Example 1:Byte Output data Input data0 0x00 0x001 0x01 (Status query) 0x012 0x00 0x003 0x07 (COL_ID) 0x07 (COL_ID_SEL)4 0x01 (MET_ID_1) 0x01 (MET_ID_1_SEL)5 0x02 (MET_ID_2) 0x02 (MET_ID_2_SEL)6 0x03 (MET_ID_3) 0x03 (MET_ID_3_SEL)7 0x04 (MET_ID_4) 0x04 (MET_ID_4_SEL)8 --- DC current L1 [7:0]9 --- DC current L1 [15:8]10 --- DC current L1 [23:16]11 --- DC current L1 [31:24]12 --- DC current L2 [7:0]13 --- DC current L2 [15:8]14 --- DC current L2 [23:16]15 --- DC current L2 [31:24]16 --- DC current L3 [7:0]17 --- DC current L3 [15:8]18 --- DC current L3 [23:16]19 --- DC current L3 [31:24]20 --- DC voltage L1-N [7:0]21 --- DC voltage L1-N [15:8]22 --- DC voltage L1-N [23:16]23 --- DC voltage L1-N [31:24]