88 Commissioning WAGO-I/O-SYSTEM 750750-494 3-Phase Power Measurement ModuleManualVersion 1.2.08.1.5 "Factory Settings" TabAfter entering a password (see "Energy" tab above), you can reset all parametersof the I/O module to their factory settings on the "Factory Settings" tab.List of factory settingsA list of factory settings may be found in section “Appendix”.Use I/O Module Settings [Restore] to reset the I/O module settings only.Calibration data remains unchanged.Use Calibration Data [Restore] to reset the calibration data only. The I/O modulesettings remain unchanged.Use Total [Restore] to reset all I/O module settings and calibration data.These actions are carried out immediately and cannot be undone. Therefore, the[Save] button is disabled at the bottom of the window.Figure 26: “Factory Settings” Tab