InformationAdapting the parameter modifies the deceleration path V_3 R V_1. The recalculated path is shown inthe display. If necessary, correspondingly adapt the interrupt point for V_3.12.9 Crawl path optimizationImprovement of:• too long crawl paths with traveling speed V_1• non-flush stopping due to V_1 being prematurely switched offwithout additional installation work.Using the crawl path optimization in the menu:Decelerating / S_DI1Decelerating / S_DI2Decelerating / S_DI3the traveling speeds V_1, V_2 and V_3 are switched off in all floors delayed by the value configured inthe corresponding menu.Optimizing the crawl paths1 Travel to each floor from both directions of travel with the max. traveling speedV_3 or V_2 and check the crawl path s1 in the "INFO / Page 03" menu.Dist. - - - - - - - - - - - 03sa: 0.00 s21 0.52msr:^0.00 s31: 1.45ms1: 0.00 sd: 0.52m2 The value for s1 should be the same for all floors from both travel directions.If the crawl paths differ, use the smallest value for s1.3 In the Decelerating menu, change the values for "S_DI3" or "S_DI2" to thatdetermined for s14 Check the deceleration behaviour and correct the values for the parameters"S_DI3" or "S_DI2" if necessary.InformationIf s1 has different values, it is not possible to get the same crawl path in all floors!Translation of the original operating instructionsZETADYN 4C Travel optionsR-TBA12_01-GB 1415 Part.-No. 00163371-GB113/20412Travel options