Scroll through fault list:the fault list can be scrolled through using the two arrow keys.Scroll up (reduce fault serial number)Scroll down (increase fault serial number)Determine time of faultWhen i key is pressed, the difference from the current number oftravels and operting time is displayed" BC:Alarm/fault 3E912 S422 -2.4h-0000189 12C" 01 RV1 0.00m +12AIn CANopen lift and DCP operation, the time at which an error occurs is saved in the error list anddisplayed.? B R : F a h r t - F e h l e r ?E 5 8 3 S 4 3 0 1 0 : 3 00 0 0 0 0 7 6 x x x 2 8 C? 0 0 R V 1 5 . 9 1 m + 1 2 A11 Time at which the error occurred14.4 Delete error memoryThe fault memory is wiped by means of an entry in the Statistic/ST_CLR=ON.The following parameters are reset:• ST_LST (Error list)• ST_RES (Number of interruptions in the mains supply)• ST_SRF (Number of trip interruptions due to an interruption in the control enabling)• ST_SCO (Number of trip interruptions due to an interruption in the contactor monitor)14.5 Error listAll error messages are stored in the Statistic / ST_LST menu (see "Error diagnosis / error memory"chapter)14.5.1 Masc-FunktionYou can deactivate individual monitoring functions by inputting an item in the error mask (see"Parameter list/Monitoring" menu chapter). To do this, enter the corresponding error number into errormasks 1-5.The maskable errors are marked in the error list with a point in thecolum n M.CAUTION!Caution!The mask function may only be used for troubleshooting and error diagnostics. The corre-sponding error cause must be eliminated in order to ensure continuous service of the fre-quency inverter!Sequential errors can occur if errors are masked.The masking deactivates important monitoring functions. This may result in dangerous operat-ing states or damage to the frequency inverter.Translation of the original operating instructionsZETADYN 4C Error diagnosisR-TBA12_01-GB 1415 Part.-No. 00163371-GB131/20414Error diagnosis