Actual signals and parameters12466.07 TORQ MEM SMPL PTR Defines the source or constant for selection PARAM 66.07 of66.01 TORQUE MEM SAMPLE.-255.255.31…+255.255.31/ C.-32768…C.32767Parameter index or a constant value. See 10.05 EXT1 STRT PTR forinformation on the difference.-66.08 TORQ MEM ENBL PTR Defines the source or constant for selection PARAM 66.08 of66.02 TORQUE MEM ENABLE.-255.255.31…+255.255.31/ C.-32768…C.32767Parameter index or a constant value. See 10.05 EXT1 STRT PTR forinformation on the difference.-67 LEAD CTRL Winder Lead macro specific parameters.Note: This group is hidden unless WINDER LD MACRO is selected67.01 WEB SPD INPUT Selects the signal source for the web speed feedback.NOT SEL Not selected. 1AI1 Analog input AI1 (voltage). 2AI2 Analog input AI2 (current). 3AI3 Analog input AI3 (current). 4AI5 Analog input AI5 (voltage or current). 5AI6 Analog input AI6 (voltage or current). 667.02 WEB SPD SCALE Scales the AI maximum (10 VDC / 20 mA) to motor speed at core.0…9999.0 Setting range. 10 = 170 DDCS CONTROL Settings for the fiber optic channels.70.01 CH0 NODE ADDR Defines the node address for channel 0. No two nodes on-line mayhave the same address. The setting needs to be changed when amaster station is connected to channel 0 and it does not automaticallychange the address of the slave. Examples of such masters are anABB Advant Controller or another drive.0…254 Address. 1 = 170.02 CH0 BAUD RATE The communication speed of channel 0.8 Mbit/s 8 megabits per second. 04 Mbit/s 4 megabits per second. 12 Mbit/s 2 megabits per second. 21 Mbit/s 1 megabits per second. 370.05 CH2 NODE ADDR Defines the node address for channel 2.1…125 Setting range. 1 = 170.06 CH2 M/F MODE Selects how the drive will use CH2 in a Master/Follower ring.NOT IN USE CH2 is not used. 1MASTER The drive is the master of the ring. 2FOLLOWER The drive is a follower and receives the data sent from the Master asdefined in the Master’s master signal 1, 2, and 3.3SPD FOLLOWER See selection FOLLOWER. The speed reference of the drive isautomatically set to follow the master, regardless of the setting in11.03 EXT1 REF SELECT.4SPDTQ FOLLOW See selection SPD FOLLOWER. The torque reference of the drive isautomatically set to follow the master.570.07 MASTER SIGNAL 1 Signal pointer for high speed dataset communications to followers ascommand word.No. Name/Value Description FbEq