Actual signals and parameters72DI5 See selection DI2. 5DI6 See selection DI2. 6DI7 See selection DI2. 7DI8 See selection DI2. 8DI9 See selection DI2. 9DI10 See selection DI2. 10DI11 See selection DI2. 11DI12 See selection DI2. 12FIELDBUS See selection DI2. Instead of a digital input, the selection comes from06.01 DATASET 1 WORD 1 bit 09. See chapter Fieldbus control.13PARAM 12.09 Source selected by 12.09 TAKE-UP/PAYOUT PTR 1412.07 SPEED CHANGE Defines take-up/payout speed adder.+/- 11.05 EXT1 REF MAX Setting range. 1 = 1 rpm12.08 CNST SPD RUN SEL Selects if the drive is to start when the digital inputs used in 12.01CONST SPEED SEL = 1 or if the run command is required.MNSTRT REQ A separate run command is required to start the drive. 0STRT W/CNST The drive starts when the constant speed digital input = 1. 112.09 TAKEUP/PAYOUT PTR Defines the source or constant for selection PARAM 12.09 of12.06 TAKEUP/PAYOUT-255.255.31…+255.255.31/ C.-32768…C.32767Parameter index or a constant value. See 10.05 EXT1 STRT PTR forinformation on the difference.-13 ANALOG INPUTS The analog input signal processing13.01 MINIMUM AI1 Defines the minimum value for analog input AI1. When used as areference, the value corresponds to the reference minimum setting.Example: If AI1 is selected as the source for external reference 1, thisvalue corresponds to the value of 11.04 EXT1 REF MINIMUM.0 V Zero Volts.Note: The program cannot detect a loss of analog input signal.12 V Two Volts 2TUNED VALUE The value measured by the tuning function. See selection TUNE. 3TUNE The value measurement triggering. Procedure:- Connect the minimum signal to input.- Set the parameter to TUNE.Note: The readable range in tuning is 0 V to 10 V.4No. Name/Value Description FbEq