Actual signals and parameters7514.11 RO3 TON DELAY See 14.03 RO1 TON DELAY. 1 = 1 s14.12 RO3 TOFF DELAY See 14.04 RO1 TOFF DELAY. 1 = 1 s14.13 RO4 POINTER See 14.01 RO1 POINTER. -14.15 RO5 POINTER See 14.01 RO1 POINTER. -14.17 RO6 POINTER See 14.01 RO1 POINTER. -14.19 RO7 POINTER See 14.01 RO1 POINTER. -15 ANALOG OUTPUTS The analog output signal processing15.01 AO1 POINTER The analog output is controlled by use of “pointers”. This parameterselects the word that is the desired output. Example:+.001.002.00 = MOTOR SPEED FILT.-255.255.31…+255.255.31/ C.-32768…C.32767Parameter index or a constant value. See 10.05 EXT1 STRT PTR forinformation on the difference.-15.03 MINIMUM AO1 Defines the minimum value of the analog output signal AO1.0 mA Zero mA. 14 mA Four mA. 210 mA Ten mA. 50% offset on 0 to 20 mA for testing or indication of direction. 315.04 FILTER AO1 ms Defines the filtering time constant for analog output AO1.Note: Even if you select 0 s as the minimum value, the signal is stillfiltered with a time constant of 10 ms due to the signal interfacehardware. This cannot be changed by any parameters.0 …10000 ms Filter time constant 1 = 1 ms15.05 NOM VALUE AO1 When the value of the signal selected in 15.01 AO1 POINTER 1equals this parameter, the output = 20 mA.0…65535 Setting range. 10 = 115.06 AO2 POINTER See 15.01 AO1 POINTER. -15.08 MINIMUM AO2 See 15.03 MINIMUM AO1. 1…315.09 FILTER AO2 ms See 15.04 FILTER AO1 ms. 1 = 1 ms15.10 NOM VALUE AO2 See 15.05 NOM VALUE AO1. 10 = 115.11 AO3 POINTER See 15.01 AO1 POINTER. -15.13 MINIMUM AO3 See 15.03 MINIMUM AO1. 1…315.14 FILTER AO3 ms See 15.04 FILTER AO1 ms. 1 = 1 ms15.15 NOM VALUE AO3 See 15.05 NOM VALUE AO1. 10 = 115.16 AO4 POINTER See 15.01 AO1 POINTER. -15.18 MINIMUM AO4 See 15.03 MINIMUM AO1. 1…315.19 FILTER AO4 ms See 15.04 FILTER AO1 ms. 1 = 1 ms15.20 NOM VALUE AO4 See 15.05 NOM VALUE AO1. 10 = 1No. Name/Value Description FbEq63%100T tFiltered SignalUnfiltered Signal O = I · (1 - e -t/T)I = filter input (step)O = filter outputt = timeT = filter time constant